© Brighteon.com All Rights Reserved. All content posted on this site is commentary or opinion and is protected under Free Speech. Brighteon is not responsible for comments and content uploaded by our users.
AMI Meter
• The AMI measured current does not have a one for one relationship between current
consumed and indicated reading. This must be measured via an electronic sensor,
converted to a digital signal and then a computer calculation averages all of the sensor
input and posts the data in computer memory and the reading on the LCD display. There is
a manipulation of the indicated reading that can be affected by many factors.
• All electronics components are rated between 1% to 20% accuracy. Most of the
components on the AMI meters are 5% rated, with the current transformers rated at 1%
accuracy within the permitted range of temperatures. I will point out that this 1% is only
related to temperature not the measured load characteristic. This is important because
testing at the University of Twente in 2016 showed very high smart meter inaccuracies of
582% (https://www.utwente.nl/en/news/2017/3/313543/electronic-energy-meters-falsereadings-almost-six-times-higher-than-actual-energy-consumption) with current
transformers, such as in the all AMI meters, are generally accurate to within ±10%. That is a
20% range. So professions by utilities that the AMI is more accurate is highly suspect and
only true in a very tightly controlled setting such as ten 100 watt incandescent bulbs. Not
with electronic appliances, motors, CFL’s, LED’s etc. (note a 100 watt light bulb can vary
10%




